10.6 JP/GP.WRITE (Writing Data to the Programmable Controller on Another Station)
10.6 JP/GP.WRITE (Writing Data to the Programmable
Controller on Another Station)
This instruction writes data to the device of the programmable controller on another station. (In units of words)
*1 T, C, D, W, ST, SD, and SW can be used.
When specifying SD/SW, data can be written in the range that the user can set.
For details on SD/SW, refer to the following.
Manuals for the CPU module and network module of the target station
(1) Setting data
Setting data
Available devices
Internal device (System, user) Constant
Others
Bit Word K, H
(S1) 
(S2) 
(D1)
*1
(D2)
Setting data Description Set by Data type
Jn
Own station's network No. (1 to 239, 254)
254: Network specified in Valid Module During Other Station
Access
User
16-bit binary
Un
Start I/O number of the master/local module of the own station
(00 to 3E
H
: Upper 2 digits of the I/O number expressed in 3 digits)
(S1)
Start device of the own station where control data is stored
( Page 176, Section 10.6 (1) (a))
Device name
(S2)
Start device of the own station where data to be written is stored
( Page 179, Section 10.6 (1) (b))
(D1)
Start device of the target station where data is to be written
(A continuous area for with the write data length is required.)
( Page 179, Section 10.6 (1) (c))
System
(D2)
Device of the own station, which is turned on for 1 scan upon
completion of the instruction.
(D2)+1 is turned on as well when the instruction fails.
Bit
JP.WRITE
Start contact
GP.WRITE
Start contact
JP.WRITE Jn
GP.WRITE Un
or
""
or
""
(S1)
(D1)
(D1)
(D1)
(D1)
(S2) (D2)
(S1) (S2) (D2)