CHAPTER 7 PARAMETER SETTING
7
7.5 Refresh Parameters
Transfer SB
Transfer
SW
Dev. name
Select link refresh ranges of SB and SW. Link refresh range can be
set for both "Transfer SB" and "Transfer SW" by 1. ( Page 104,
Section 8.2.2)
(1) Transfer SB
• Link side: Fixed at "SB".
• PLC side: M, B, D, W, SB
(2) Transfer SW
• Link side: Fixed at "SW".
• PLC side: M, B, D, W, SW
(Default: Blank)
Points,
Start, End
• Link side: 0 to 1FF
H
• PLC side: Within device range of
safety CPU module
(Default: Blank)
Set bit devices in increments of 16
points and word devices in increments
of 4 points.
Transfer 1
to 8
Dev. name
Select link refresh ranges of RX, RY, RWr, and RWw. Link refresh
ranges can be set up to 8. ( Page 104, Section 8.2.2)
• Link side: RX, RY, RWr, RWw
• PLC side:
When RX is set to “Link Side”:
X, M, B, D, W
When RY is set to “Link Side”:
Y, M, B, T, C, ST, D, W
When RWr is set to “Link Side”:
M, B, D, W
When RWw is set to “Link Side”:
M, B, T, C, ST, D, W
(Default: Blank)
Points,
Start, End
• Link side:
0 to 3FFF
H
for RX/RY
0 to 1FFF
H
for RWr/RWw
• PLC side: Within device range of
safety CPU module
(Default: Blank)
Set bit devices in increments of 16
points and word devices in increments
of 4 points.
button
Reset refresh parameters to default.
Item Description Setting range
Ex.
0000
H
Device
name
(SB)
Transfer
SB
Transfer
SW
01FFH
Master/local module Safety CPU module
0000H
01FFH
0000H
01FFH
0000H
01FFH
Device
name
(SW)
Device
name
(SB)
Device
name
(SW)
Ex.
Device
name
(RX)
Device
name
(RY)
Device
name
(RWr)
Device
name
(RWw)
Device
name
(W)
Device
name
(W)
Device
name
(Y)
Device
name
(X)
Transfer
1
Transfer
2
Transfer
3
Transfer
4
Master/local module Safety CPU module
0000
H
00FF
H
0000
H
00FF
H
1000
H
10FF
H
0000
H
00FF
H
1000
H
10FF
H
0000
H
00FF
H
0000
H
00FF
H
0100
H
01FF
H