CHAPTER 9 CC-Link IE FIELD NETWORK DIAGNOSTICS
9
9.2 Starting Diagnostics
9.2 Starting Diagnostics
This section describes how to use CC-Link IE Field Network diagnostics.
1. Connect GX Developer to the safety CPU module.
If a slave station cannot be monitored due to an error such as cable disconnection, directly connect a
programming tool, which is supported by the programmable controller used, to the slave station.
Connect GX Works2 to a slave station that uses a standard programmable controller, and connect GX
Developer to a slave station that uses a safety programmable controller.
2. Start CC-Link IE Field Network diagnostics from the menu.
[Diagnostics] [CC IE Field diagnostics]
When another station has been specified as a connected station
CC-Link IE Field Network diagnostics cannot be started when another station has been specified in "Other Station
Setting" of the "Transfer Setup" window. Directly connect a programming tool, which is supported by the programmable
controller used, to the target station, and start CC-Link IE Field Network diagnostics.
Start from the "System Monitor" window
CC-Link IE Field Network diagnostics can also be started from the "System Monitor" window.
Click the master/local module. Click the button.