D216
H
to D217
H
Transient data command error Correct the request command at the request source, and retry the operation.
D218
H
Incorrect number of read/write
transient data
Correct the number of read/write device data at the request source, and retry
the operation.
D219
H
Transient data attribute code error Correct the attribute code at the request source, and retry the operation.
D21A
H
Transient data access code error Correct the access code at the request source, and retry the operation.
D21B
H
to D21C
H
Transient data request error
• Abnormal transient data were issued from the CPU module.
• Replace the CPU module and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D21D
H
Network No. error in transient
transmission
• A cable test cannot be executed for a different network. Correct "Testing
Station Setting", and execute the cable test again.
• Transient data that cannot be sent to a different network were received.
Correct the network number or the target station number at the request
source, and retry the operation.
D21E
H
Target station No. error in transient
transmission
• A communication test cannot be executed on a sending (relay) station.
Correct the "Target Station" setting, and execute the communication test
again.
• Transient data of the application type that cannot be executed on the own
station were received. Correct the application type or the target station
number at the request source, and retry the operation.
D21F
H
Network module failure
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D220
H
No master station Add a master station to the network.
D222
H
Transient data command error Correct the request command at the request source, and retry the operation.
D223
H
Transient error
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• If the request source is on another network, check if the routing
parameters are correctly set.
• If this error persists, please consult your local Mitsubishi representative.
D22E
H
Station No. setting not available for the
target station
• Although change of the target station number was attempted online from
the master station, the target station does not have the online station
number setting function.
• Check the manual for the target station if the station number setting
function is available.
• If the function is supported by the model, please consult your local
Mitsubishi representative.
D22F
H
No baton pass executed in the target
station
Check the communication status of the station whose station number is to be
changed.
D230
H
Invalid station No. setting
• The station number change was attempted for the own station (master
station).
• Check that no station number is set for the target station.
D231
H
Station No. already set in the target
station
• The station number has been already set for the target station.
• Check that no station number is set for the target station.
D232
H
Station No. setting target not exist
• The station where the station number change was attempted does not
exist.
• Check that no station number is set for the target station.
D233
H
Station No. setting out of range Set the station number within 1 to 120, and retry the operation.
Error code Error Action