Mitsumi electronic QS07J1GF11-T2 Drums User Manual


 
274
Number Name Description
Availability
Master
station
(safety
station)
Local
station
SB0000 Link start (own station)
The own station's cyclic transmission is restarted.
OFF: No start direction
ON: Start direction (enabled during start-up)
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is off.
• For SB0000 to SB0003, this is enabled when only one of them is
turned on.
SB0001 Link stop (own station)
The own station's cyclic transmission is stopped.
OFF: No stop direction
ON: Stop direction (enabled during start-up)
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is off.
• For SB0000 to SB0003, this is enabled when only one of them is
turned on.
SB0002 System link start
Cyclic transmission of the entire system is restarted.
The station where cyclic transmission is restarted is specified by the Link
stop/start direction (SW0000 to SW0008).
OFF: No start direction
ON: Start direction (enabled during start-up)
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is off.
• For SB0000 to SB0003, this is enabled when only one of them is
turned on.
×
SB0003 System link stop
Cyclic transmission of the entire system is stopped.
The station where cyclic transmission is stopped is specified by the Link
stop/start direction (SW0000 to SW0008).
OFF: No stop direction
ON: Stop direction (enabled during start-up)
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is off.
• For SB0000 to SB0003, this is enabled when only one of them is
turned on.
×
SB0006
Clear communication
error count
Clears the link special registers for the communication error (SW0068 to
SW006B, SW0074 to SW0077, SW007C to SW007F, SW0120 to
SW0127, SW0130 to SW0137, SW0140 to SW0147, and SW0150 to
SW0157).
OFF: No clear direction
ON: Clear direction (valid while this relay is on)
SB0009 Event count clear
This clears the Event history status (SB007A) and Event count
(SW007A).
OFF: No clear direction
ON: Clear direction (Errors are not counted while this is ON.)
SB0010
Temporary error invalid
request
Stations specified in Reserved station function disable/temporary error
invalid station setting (SW0010 to SW0017) are set as temporary error
invalid stations.
OFF: No request
ON: Request issued
×