Mitsumi electronic QS07J1GF11-T2 Drums User Manual


 
291
APPENDICES
A
Appendix 4 Link Special Register (SW) List
SW0059
Number of total slave
stations (current value)
Stores the number of total slave stations that are actually connected by
data link in CC-Link IE Field Network.
Range: 1 to 120 (0 when own station is disconnected)
SW005A
Maximum baton pass
station
Stores the maximum station No. of the stations where the baton pass is
performed.
Range: 1 to 120 (0 when own station is disconnected)
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
SW005B
Maximum cyclic
transmission station
Stores the maximum station No. of the station where the cyclic
transmission is performed.
Range: 1 to 120 (0 when own station is disconnected)
(Condition)
• This is enabled when Data link status (own station) (SB0049) is off.
SW0060 Maximum link scan time
Stores the maximum value of the link scan time during cyclic
transmission. (Unit: ms)
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
SW0061 Minimum link scan time
Stores the minimum value of the link scan time during cyclic
transmission. (Unit: ms)
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
SW0062 Current link scan time
Stores the current value of the link scan time during cyclic transmission.
The stored value contains a maximum error of 1 ms. (Unit: ms)
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
SW0063
Constant link scan set
value
Stores the setting value of the contact link scan that is set in the
supplementary setting.
0: No setting
1 to 200: Setting value of contact link scan time (Unit: ms)
(Condition)
• This is enabled when Data link status (own station) (SB0049) is off.
Number Name Description
Availability
Master
station
(safety
station)
Local
station