Mitsumi electronic QS07J1GF11-T2 Drums User Manual


 
115
CHAPTER 8 FUNCTIONS
8
8.2 Cyclic Transmission
8.2.6 Output status setting for CPU module STOP
8.2.6 Output status setting for CPU module STOP
When the safety CPU module mounted with a master/local module is set to STOP, whether cyclic data output is held or
cleared can be selected.
(1) Active range
Depending on the device set for link refresh, the output status is fixed to hold or clear regardless of the setting in
"Output Setting During CPU STOP".
The table below shows a relationship between the output status of devices set for link refresh and "Output Setting
During CPU STOP".
(2) Setting method
Set the output status for the case where the safety CPU module switch is set to STOP. Select hold or clear in
"Network Operation Setting". ( Page 85, Section 7.4)
(3) Precautions
(a) When "Output Setting During CPU STOP" is set to clear
When the safety CPU module is on the STOP status, data cannot be forcibly output to a slave station by GX
Developer.
For output of safety communication, the content set in "Output Setting During CPU STOP" is active only when the safety
CPU operation mode is on the test mode. Under the safety mode, output is cleared regardless of the setting.
Link refresh device
Output setting during CPU STOP
Hold Clear (ALL OFF)
RY
Y Clear Clear
Other than Y Hold Clear
RWw All available devices Hold Hold