(1) Performance specifications comparison
Item
Specifications
CC-Link Safety master module
(QS0J61BT12)
Master/local module
(QS0J71GF11-T2)
Number of
connectable
stations per
network
Safety master station
or
Master station (safety station)
1 station
(Up to 64 remote stations can be
connected to the safety master station.)
1 station
(Up to 120 slave stations can be
connected to the master station (safety
station).)
Local station (standard station) 120 stations
Maximum link points per network
RX 2048 points 16384 points
RY 2048 points 16384 points
RWr 256 points 8192 points
RWw 256 points 8192 points
Maximum link
points per station
Own station:
Safety master station
or
Master station (safety
station)
RX 2048 points 16384 points
RY 2048 points 16384 points
RWr 256 points 8192 points
RWw 256 points 8192 points
Own station:
Local station
RX 2048 points
RY 2048 points
RWr 1024 points
RWw 1024 points
Receiving station:
Safety remote station
RX 32 points
RY 32 points
RWr 0 points
RWw 0 points
Receiving station:
Standard remote
station
RX 128 points
RY 128 points
RWr 16 points
RWw 16 points