(b) Modified functions
The following are the functions modified in the master/local module.
Function Note for replacement
Slave station cut-off function
When the master/local module is connected in line topology, stations placed after the
disconnected station become data link faulty station. To prevent disconnection of normal
stations, connect CC-Link IE Field Network in star topology.
( Page 49, Section 5.1.1 (2))
Standby master function This function is not available for the master/local module.
Data link status setting if the CPU module
on the master station is faulty
This setting is fixed to "Continue" for the master/local module.