(1) Setting data
(a) Control data
The control data of the SWRITE instruction control data is the same as that of the WRITE instruction
( Page 175, Section 10.6)
(b) Start device of the own station where data to be written is stored
The start device of the own station where data to be written by the SWRITE instruction is stored, is the same as
that of the WRITE instruction ( Page 175, Section 10.6)
(c) Start device of the target station where data is to be written
The start device of the target station, is the same as that of the WRITE instruction
( Page 175, Section 10.6)
Setting data Description Set by Data type
Jn
Own station's network No. (1 to 239, 254)
254: Network specified in Valid Module During Other Station Access
User
16-bit binary
Un
Start I/O number of the master/local module of the own station
(00 to 3E
H
: Upper 2 digits of the I/O number expressed in 3 digits)
(S1)
Start device of the own station where control data is stored
( Page 188, Section 10.7 (1) (a))
Device name
(S2)
Start device of the own station where data to be written is stored
( Page 188, Section 10.7 (1) (b))
(D1)
Start device of the target station where data is to be written
(A continuous area with the write data length is required.)
( Page 188, Section 10.7 (1) (c))
System
(D2)
Device of the own station, which is turned on for 1 scan upon
completion of the instruction.
(D2)+1 is turned on as well when the instruction fails.
Bit
(D3)
Device of the target station, which is turned on for 1 scan upon
completion of the instruction.
(Data writing from another station can be confirmed.)