Mitsumi electronic QS07J1GF11-T2 Drums User Manual


 
234
(13)Setting/Canceling a temporary error invalid station
Setting/Canceling a temporary error invalid station is executed by CC-Link IE Field Network diagnostics, but can
also be executed through link special relays (SB) and link special registers (SW). ( Page 146, Section 9.7)
(a) Setting a temporary error invalid station
1. Specify the station number to set a temporary error invalid station in Reserved station function
disable/temporary error invalid station setting (SW0010 to SW0017),
2. Turn on Temporary error invalid request (SB0010).
3. Temporary error invalid request accept status (SB0058) is turned on.
4. When a temporary error invalid station is set, Temporary error invalid setting completion status
(SB0059) turns on.
5. Temporary error invalid station status (SB00E0) turns on, and the station No. of the temporary
error invalid station is stored in Temporary error invalid station status (SW00E0 to SW00E7).
6. When the temporary error invalid station is set with error, an error code will be stored in
Temporary error invalid station setting result (SW0054).
7. Turn off Temporary error invalid request (SB0010).
(b) Canceling a temporary error invalid station
1. Specify the station number to cancel a temporary error invalid station in Reserved station function
disable/temporary error invalid station setting (SW0010 to SW0017).
2. Turn on Temporary error invalid setting cancel request (SB0011).
3. Temporary error invalid setting cancel request accept status (SB005A) is turned on.
4. When the cancellation is completed, Temporary error invalid setting cancel completion status
(SB005B) turns on.
5. Use Temporary error invalid station setting (SW00E0 to SW00E7) to check whether the temporary
error invalid station is cancelled. When the network no longer has a temporary error invalid
station, Temporary error invalid station status (SB00E0) is turned off.
6. When the temporary error invalid station is cancelled with error, an error code will be stored in
Temporary error invalid station setting cancel result (SW0055).
7. Turn off Temporary error invalid setting cancel request (SB0011).
Number Description Number Description
SB0010 Temporary error invalid request
SW0010 to
SW0017
Reserved station function disable/temporary error
invalid station setting
SB0058 Temporary error invalid request accept status SW0054 Temporary error invalid station setting result
SB0059 Temporary error invalid setting completion status
SB00E0 Temporary error invalid station status
SW00E0 to
SW00E7
Temporary error invalid station setting
Number Description Number Description
SB0011 Temporary error invalid setting cancel request
SW0010 to
SW0017
Reserved station function disable/temporary error
invalid station setting
SB005A
Temporary error invalid setting cancel request accept
status
SW0055 Temporary error invalid station setting cancel result
SB005B
Temporary error invalid setting cancel completion
status
SB00E0 Temporary error invalid station status
SW00E0 to
SW00E7