Mitsumi electronic QS07J1GF11-T2 Drums User Manual


 
256
D62D
H
Data link start failed
Data link start failed due to any of the following causes. Remove the error
cause, and retry the operation.
• Station No. not set
• CPU module error on the own station
• Master station duplication
• Station type mismatch
• Master station lost
• Own station No. out of range
• Station No. duplication (own station)
• Own station reserved
• Parameter error
• Parameter communication in progress
• Parameters not received (master station only and no slave station exists)
• Link stop command
D630
H
Network module failure
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D701
H
Temporary reserved station
cancel/temporary error invalid station
setting not set
Set the target station(s) in Reserved station function disable/temporary error
invalid station setting (SW0010 to SW0017), and retry the operation.
D706
H
Request error of temporary error
invalid station setting/cancel or
reserved station cancel/restoration
(when the own station is a local
station)
Temporary error invalid station setting/cancel or reserved station
cancel/restoration cannot be executed from a local station. Retry the
operation from the master station.
D70B
H
Request error of temporary error
invalid station setting/cancel or
reserved station cancel/restoration
(when different settings are
simultaneously performed)
• Temporary error invalid station setting/cancel using SB0010 and SB0011
or reserved station cancel/restoration using SB0012 and SB0013 cannot
be simultaneously executed.
• Retry the operation so that only one bit in SB0010 to SB0013 may turn on
after all bits in them are turned off.
D720
H
Data link start/stop instruction out of
range
Check the setting, and stop or start data link.
D721
H
Data link start/stop retry error (another
station)
Retry the operation after the stop or restart of data link is completed.
D722
H
Data link start/stop retry error (own
station)
D723
H
Data link start/stop retry error (entire
system)
D724
H
Data link start/stop station error Check the setting, and stop or start data link.
D725
H
Station type error (station that
starts/stops data link throughout the
entire system)
A local station cannot start or stop data link of all or multiple stations.
Perform these operations from the master station.
D726
H
Transient data command error Correct the request command at the request station, and retry the operation.
D727
H
Data link start/stop command-
instructing stations different
• Data link start was instructed from a station different from the one that had
instructed the data link stop. Instruct data link start and data link stop from
the same station.
• The method of the data link start differs from that of the data link stop.
Instruct the data link start using the same method as the data link stop
( Data link is stopped using the CC-Link IE Field Network diagnostics,
and the data link is started using a program).
• Data link start failed. Forcibly restart the data link.
Error code Error Action
Ex.