Tektronix VX4101A Drums User Manual


 
SCPI Commands for the SurePatht Modules
3–280
VX4101A MultiPaq Instrument User Manual
[ROUTe:]CONFigure:DISJoin
Two additional VX4330 modules are installed in consecutive slots to the right of
the VX4101A.
Command Response
route:configure:disjoin m1 Disconnect the commons of the first scanner
[ROUTe:]CONFigure:JOIN
Two additional VX4330 Modules are installed in consecutive slots to the right of
the VX4101A.
Command Response
route:configure:join m1,(1:3) Connect the commons of sections 1, 2, and 3 on the first
VX4330
route:close:mode
scan,m2,(1:4)
Set the mode of operation of sections 1 through 4 on the se-
cond VX4330 to scan mode. In this mode, only one relay is a
section is closed at a time
route:conf twire,m2,(1:4) Configure sections 1 through 4 on the second VX4330 as
20-to-1 2-wire scanners
route:conf:join m2,(1:4) Connect the commons of sections 1 through 4 on the second
VX4330. Since these sections have been set to operate in the
scan mode, and have been configured as 20-to-1 2-wire scan-
ners, these sections now comprise a single 80-to-1 2-wire
scanner
route:close (@m2(10!1)) Close channel 10 of section 1 of the second VX4330
route:close (@m2(2!4)) Close channel 2 of section 4 of the second VX4330. Since the
first four sections of this module are joined and are set to oper-
ate in the scan mode, all relays in sections 1 through 4 of this
module are opened before this relay is closed
[ROUTe:]ID?
A VX4330, VX4380, and VX4320 are installed in consecutive slots to the right
of the slot containing the VX4350. The default module names for the VX4350,
VX4380, VX4330, and VX4320 in this configuration are m1, m2, m3, and m4
respectively. These module names may be altered with the [ROUTe:]MOD-
ule:DEFine command.
Command Response
route:id? VX4350, VX4380, VX4330, VX4320
route:module:Catalog? “M1”, “M2”, “M3”, “M4”
route:close (@m1(1)) Close relay number 1 on the VX4350